  Do you need pat testing service around london south?

Our aim is to provide Companies, Organisation's,
and Businesses with a comprehensive and trouble free,
realistically priced service that complies with all of the following

PAT TEST REGULATIONS

The Health and Safety at Work Act 1974
The Electricity at Work Regulations 1989
The Provision and Use of Work Equipment Regulations 1998
The Management of Health and Safety at Work Regulations 1999

 
TESTING FREQUENCIES

Portable Appliance Testing ~ Electrical Testing ~ Electrical Safety Testing

 
This site uses Adobe Reader. Please click the link below to install the software if you don't have it installed on your computer.

 
  Adobe Reader  

Frequancy Table






Equipment Class Inspection and tests Offices and shops Hotels Schools






Handheld Class I and II User checks Before use Before use Before use

Class I Formal visual insp. Every 6 months Every 6 months Every 4 months


Combined insp. and test Every year Every year Every year

Class II Formal visual insp. Every 6 months Every 6 months Every 4 months


Combined insp. and test None None Every 4 years






Portable Class I and II User checks Weekly Weekly Weekly

Class I Formal visual insp. Every year Every year Every 4 months


Combined insp. and test Every 2 years Every 2 years Every year

Class II Formal visual insp. Every 2 years Every 2 years Every 4 months


Combined insp. and test None None Every 4 years






Moveable Class I and II User checks Weekly Weekly Weekly

Class I Formal visual insp. Every year Every year Every 4 months


Combined insp. and test Every 2 years Every 2 years Every year

Class II Formal visual insp. Every 2 years Every 2 years Every 4 months


Combined insp. and test None None Every 4 years






Stationary Class I and II User checks None None Weekly

Class I Formal visual insp. Every 2 years Every 2 years None


Combined insp. and test Every 4 years Every 4 years Every year

Class II Formal visual insp. Every 2 years Every 2 years Every year


Combined insp. and test None None Every 4 years






IT Class I and II User checks None None Weekly

Class I Formal visual insp. Every 2 years Every 2 years None


Combined insp. and test Every 4 years Every 4 years Every year

Class II Formal visual insp. Every 2 years Every 2 years Every year


Combined insp. and test None None Every 4 years






User checks






The person using the equipment must carry out user checks at regular intervals; these Intervals can be viewed in The Frequency table.






The user should look for trapped cables, bad connections in the plug or appliance, brakes in the cable supplying the appliance or is the bodywork of the appliance free from cracks and brakes.






The use of double adapters is forbidden, All appliances must be plugged into there own socket outlet or plug board.
 




It is important that extension leads and plug boards are not over load.






Where there is special equipment such as (serves, etc) it is preferred that these are plugged directly into a socket outlet and not plugboards or extension leads.This wil lprevent over equipment be plug into the same power source and causing interference.






It is important you report any faults or problems to you line manager so that the necessary action can be taken. If in any doubt please consult a qualified electrician.
 





Pat Testing ~ Appliance Testing ~ Safety Testing ~ London ~ North London


23 MORGAN MANSIONS, MORGAN ROAD, LONDON. N7 8NA
Tel 07836 582 791 Or alternatively 0207 503 4272
EMAIL: info@northernsoundhouse.com
Website designed, hosted and Listed on Ufindus.com
Website and contents copyright © 2007 www.northernsoundhouse.com All Rights Reserved.